- Output Data Format: Configurable as 16-bit integer, 32-bit integer, or IEEE 32-bit floating point
- HART Support: Integrated HART 5.0 protocol support for all channels
- Accuracy:
- ±0.25% of full scale at 25°C
- ±0.60% of full scale over 0–60°C operating range
- Output Settling Time:
- Voltage: 2 ms
- Current: 23 ms (without HART), 70 ms (with HART)
- Power Requirements:
- External field power: 19.2–30.0 VDC
- Maximum current draw: 250 mA
- Backplane current: 3 mA at 5 VDC
- Calibration: Supports automatic calibration and software-based configuration
Key Features
- Fully software-configurable channels for voltage or current output without the need for hardware jumpers
- Integrated HART modems for bidirectional communication and device diagnostics
- Alarm and clamp limit functions per channel for enhanced process monitoring
- Configurable output bias and scaling for precise signal adjustment
- Alarm latching for fault detection and system diagnostics
- Compatible with standard terminal base blocks:
- IC694TBB032 (Box-style)
- IC694TBB132 (Extended Box-style)
- IC694TBS032 (Spring-style)
- IC694TBS132 (Extended Spring-style)
- Hot-swappable design for minimal downtime during maintenance
- Mounts on any available slot in RX3i racks, including local CPU or remote I/O racks
Functional Capabilities
- Each channel can be independently configured for voltage or current mode
- Supports HART communication on current output channels (4–20 mA range)
- Real-time monitoring and diagnostics via controller software
- High-resolution signal output ensures accurate process control
- Robust design suitable for industrial environments with electromagnetic interference
Applications
- Process control systems in oil & gas, chemical, and water treatment plants
- Industrial automation in manufacturing and production lines
- Temperature, pressure, flow, and level control using analog actuators
- Integration with distributed control systems (DCS) and supervisory control and data acquisition (SCADA) systems
- Machine control requiring precise analog signal output
- Systems requiring HART-enabled field devices for remote configuration and diagnostics
Compatibility and Integration
- Part of the GE PACSystems RX3i family
- Designed for use with RX3i CPU units and universal backplane
- Programmable via Proficy Machine Edition (PME) software
- Seamless integration with other RX3i I/O modules for scalable system design
Environmental and Mechanical
- Operating Temperature: 0°C to 60°C
- Storage Temperature: –40°C to 85°C
- Relative Humidity: 5% to 95% non-condensing
- DIN rail mounting (EN 50022 standard)
- Compact design suitable for high-density control cabinets














There are no reviews yet.