Technical Specifications
-
Input Configuration: 16 single-ended or 8 differential, individually programmable
-
Input Ranges:
• Voltage: ±10 V, 0–10 V, ±5 V, 0–5 V, 1–5 V
• Current: 0–20 mA, 4–20 mA -
Resolution: 16-bit
-
Accuracy: ±0.1 % full scale @ 25 °C
-
Update Time: 200 ms for all channels
-
HART Version: 7.3 compliant, 1200/2200 Hz FSK
-
Burden Resistor: 249 Ω for current loops
-
Power Consumption:
• 5 V DC, 450 mA
• 3.3 V DC, 600 mA -
Operating Temperature: 0 °C to +60 °C
-
Dimensions: 110 mm × 66 mm × 50 mm
Functional Highlights
-
HART Integration: Built-in modems on every channel enable remote transmitter configuration and secondary variable read-back
-
Flexible Wiring: Single-ended or differential mode selectable per channel via software
-
Advanced Diagnostics: Open-wire, short-circuit, over-range, and HART status bits per channel
-
Hot Swap: Module insertion and removal under power supported
-
LED Indicators: Module OK, force, and fault status visible on front bezel
Application Scenarios
-
Process Plants: Interface with HART pressure, temperature, and flow transmitters in chemical and petrochemical facilities
-
Oil & Gas: Remote wellhead monitoring using multi-variable HART transmitters for pressure and temperature
-
Water Treatment: Acquisition of level and flow signals from HART-enabled sensors for dosing and pumping control
-
Power Generation: Turbine and boiler parameter measurement through smart HART transmitters linked to DCS and historian systems














There are no reviews yet.