Technical Specifications
-
Channels: 6 differential, isolated channel-to-channel
-
Input Ranges:
• Voltage: ±10 V, 0–10 V, ±5 V, 0–5 V, 1–5 V
• Current: 0–20 mA, 4–20 mA (249 Ω burden resistor) -
Resolution: 16-bit A/D converter
-
Accuracy: ±0.1 % full scale @ 25 °C, ±0.25 % full scale over operating temperature
-
Update Rate: 8 Hz to 1 kHz per channel, software-selectable filter
-
Diagnostics: Open wire, short circuit, over-range, under-range, rate-of-change alarms
-
Power Requirements:
• Internal: 450 mA @ 5 V DC, 600 mA @ 3.3 V DC
• External: 19.2–30 V DC, 500 mA -
Operating Temperature: 0 °C to +60 °C
-
Dimensions: 110 mm × 66 mm × 50 mm
Functional Highlights
-
Universal Input: Each channel independently selectable for voltage or current via software
-
Advanced Filtering: Programmable 8 Hz, 12 Hz, 16 Hz, 40 Hz, 200 Hz, 500 Hz, 1 kHz notch filters
-
Real-Time Diagnostics: Channel status LEDs and alarm bits for rapid fault detection
-
Hot-Swap Support: Module insertion and removal under power without system shutdown
-
Seamless Integration: Automatic data mapping into RX3i CPU memory every scan cycle
Application Scenarios
-
Process Control: Temperature, pressure, and flow transmitters in chemical and petrochemical plants
-
Water & Wastewater: Level and pH monitoring in treatment facilities
-
Energy Management: Current and voltage measurements in substations and renewable-energy inverters
-
Machine Monitoring: Vibration and load feedback on large motors and compressors