- Switching Speed:
- Turn-On Time: 0.2 ms maximum
- Turn-Off Time: 0.5 ms maximum
- Isolation: Optical isolation between backplane and field outputs (2500 VAC for 1 minute)
- Power Supply: Powered via Genius Bus for logic; field power (10–30 VDC) required for load operation
- Backplane Current Draw: 180 mA at 5 VDC
- Operating Temperature: -25°C to 70°C
- Storage Temperature: -40°C to 85°C
- Relative Humidity: 5% to 95% non-condensing
- Mounting: Standard 35 mm DIN rail
- Dimensions: Compact Genius I/O block footprint
- LED Indicators: Green OK LED and individual output status LEDs for real-time monitoring
- Short-Circuit Protection: Yes, with automatic current limiting and thermal shutdown
- Communication Protocol: GE Genius Bus (based on Data Highway Plus)
- Controller Compatibility: Compatible with Series 90-30, IC695, IC693, and other Genius-compatible controllers
- Certifications: CE, UL, CSA listed for industrial environments
Functional Features
- Provides 8 sourcing (PNP) solid-state outputs for driving DC loads such as relays, solenoids, indicator lights, and small contactors
- Solid-state design ensures long life, fast response, and high reliability without mechanical wear
- Each output includes overcurrent and short-circuit protection with self-recovery capability
- Optical isolation enhances system reliability by preventing noise and ground loop interference
- Individual output status LEDs allow for immediate visual diagnostics and troubleshooting
- No software configuration required—automatically recognized on the Genius Bus network
- High noise immunity suitable for electrically harsh industrial environments
- Supports distributed I/O deployment, reducing field wiring and control panel footprint
- Designed for seamless integration with existing GE automation systems and control networks
Applications
- Machine control systems requiring reliable DC output switching
- Factory automation lines for actuator and valve control
- Material handling and conveyor systems for motor starter and brake control
- Packaging and assembly equipment for sequence-driven operations
- Retrofit and upgrade of legacy GE Series 90-30 and Genius-based systems
- Use in water and wastewater treatment plants for pump and valve operation
- Integration into power generation and utility control panels
- OEM equipment where compact, durable output modules are essential
Installation and Environmental Considerations
- Install on a standard 35 mm DIN rail in a clean, dry, and well-ventilated enclosure
- Operate within the specified temperature and humidity range to ensure long-term performance
- Use properly sized wiring and secure terminal connections to handle load current
- Route field wiring away from high-voltage or high-noise sources to prevent interference
- Ground the module and associated equipment properly to ensure safety and signal integrity
- Apply external 10–30 VDC field power with correct polarity to avoid damage
- Terminate the Genius Bus network properly using a bus terminator (e.g., IC660BBA105K) at the last node
- Follow GE Fanuc installation and grounding guidelines for optimal system stability