- Input Type: Sinking (NPN) or sourcing (PNP) depending on common terminal configuration
- Isolation: Optical isolation between field inputs and backplane (2500 VAC for 1 minute)
- Response Time:
- Turn-On: 2.5 ms maximum
- Turn-Off: 2.5 ms maximum
- Power Supply: Powered via the Genius Bus (no external logic power required)
- Field Power: External 10–30 VDC required for input sensing
- Operating Temperature: -25°C to 70°C
- Storage Temperature: -40°C to 85°C
- Relative Humidity: 5% to 95% non-condensing
- Mounting: DIN rail (35 mm standard)
- Dimensions: Standard Genius I/O block size (compact footprint)
- LED Indicators: Green OK LED and individual input status LEDs for real-time monitoring
- Communication Protocol: GE Genius Bus (Data Highway Plus based)
- Network Compatibility: Compatible with Series 90-30, IC695, IC693, and other Genius-compatible controllers
- Certifications: CE, UL, CSA listed for industrial use
Functional Features
- Provides 8 isolated DC discrete input points for monitoring switches, pushbuttons, limit switches, and sensor outputs
- Supports both sinking and sourcing input configurations for maximum wiring flexibility
- Optical isolation protects the controller from electrical noise, voltage transients, and ground loops
- Integrated LED indicators allow for immediate visual feedback of input status and module health
- No configuration required via software; automatically recognized on the Genius Bus
- High noise immunity ensures reliable operation in electrically noisy industrial environments
- Designed for use in distributed I/O architectures, reducing wiring costs and complexity
- Operates over an extended temperature range, suitable for harsh industrial conditions
- Compatible with standard 24 VDC industrial control systems commonly used in automation
Applications
- Machine control systems for monitoring operator inputs and device status
- Factory automation lines requiring remote discrete signal acquisition
- Integration into material handling and conveyor systems for position and motion detection
- Use in packaging, assembly, and test equipment for process monitoring
- Deployment in power plants, water treatment facilities, and utility systems
- Retrofit projects involving Series 90-30 and legacy GE control platforms
- Applications requiring distributed I/O with centralized control via Genius Bus
- OEM machinery where compact, reliable input modules are essential
Installation and Environmental Considerations
- Install on standard 35 mm DIN rail in a clean, dry environment
- Ensure proper ventilation and avoid locations with excessive heat, moisture, or vibration
- Use shielded twisted-pair cable for field wiring to minimize electromagnetic interference
- Maintain separation between signal wiring and high-voltage power lines
- Connect field power supply with correct polarity to prevent damage to input circuits
- Ground the shield at one point only to prevent ground loops
- Verify bus termination at the last module in the network using a proper terminator such as IC660BBA105K
- Follow GE Fanuc wiring and grounding guidelines to ensure system reliability and safety














There are no reviews yet.