Update Time: 2 ms maximum for all channels
-
Isolation: 250 V continuous between field and logic sides
-
Power Consumption:
-
5 V backplane: 140 mA
-
24 V field: 120 mA with all outputs at 20 mA
-
-
Operating Temperature: 0 °C to 60 °C
-
Storage Temperature: –40 °C to 85 °C
-
Relative Humidity: 5 % to 95 % non-condensing
Functional Features
-
Per-Channel Configuration: Each output is software-selectable for range and type without hardware jumpers
-
HART Pass-Through: Transparent HART protocol support for digital instrument diagnostics and calibration
-
Open-Wire Detection: Automatic detection and alarm for broken field wiring on current outputs
-
Over-Range Protection: Outputs clamp to 110 % of span to protect field devices
-
Hot Swap Capability: Module removal and insertion under power without disrupting adjacent I/O
-
LED Status Indicators: Four green output-status LEDs and one red fault LED for at-a-glance diagnostics
Application Scenarios
-
Process Control Loops: Drive control valves and I/P positioners in chemical, pharmaceutical, and food & beverage plants
-
Speed Reference: Provide 4–20 mA or 0–10 V set-points to variable-frequency drives on conveyors, pumps, and fans
-
Building Automation: Regulate damper actuators and valve positions in HVAC systems
-
Water & Wastewater Treatment: Control chemical dosing pumps and sluice gate actuators based on flow or level feedback
-
Test & Calibration Stands: Generate precise analog signals to verify performance of sensors and transmitters














There are no reviews yet.